Contact Us
Home

RT250A
MLLT LIFE/ MISSTESTER
RT150
RTC25

 

 

 

 

 

 

 

 

 

 

 

Top of Page

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Page

 

 

 

 

 

 

 

 

Top of Page

 

 

Application Note


Measuring Accurate Relay Pull-in and Drop-out Voltage

Pull-in and drop-out voltage measurements of electromechanical relays may be taken manually or by automatic test equipment. Manual testing requires the adjustment of a suitable variable power supply until the relay contacts are observed to transfer. The rate of voltage application is not precisely defined or controlled, and may vary from one operator to the next or even from one test to the next by the same person. However the voltage is adjusted, though, the operator soon learns where the device is likely to operate. As that point is approached, the operator will slow the adjustment to a rate of perhaps a fraction of a volt per second. This rate of application very nearly approximates the steady state value at which the relay operates or releases and gives the best measurement result.
Utilizing automatic test equipment to do the same test requires some considerations if both the speed and accuracy offered by ATE is to be realized. A simple linear coil voltage ramp profile will introduce significant errors caused by overshoot due to the finite response time of the relay armature.

Pull-in voltage measured using a fixed ramp rate will always overshoot while drop-out voltage will always undershoot. The magnitude of error is expressed simply by:
Verror = RT
where R is ramp speed in volts/second and T is the operate or release time of the relay at the steady state value. The response time of a relay is much different at the actual pull-in or drop-out voltage than it is under normal switched conditions. Refer to the voltage profiles below.



Figure 1

Figure 1 shows the resulting error in pull-in voltage measurement caused by the long operate time of the relay. At a coil voltage of V1, the relay's operate time is b-a; a being the point at which the armature begins to move and b the point at which the equipment senses the contact closure. During this time the coil voltage overshoots by V2-V1.



Figure 2

Figure 2 shows the same process for drop-out voltage. At V1 the relay begins to release, but because of sluggish armature movement it is not detected until b-a seconds later. The result is in error by V2-V1 volts.
The reason for slow relay response at the steady state operate point is due to a weak effective spring force on the armature's mass. At voltage V1 the spring's tension is exactly equal to that imposed by the magnetic field. Since the armature has mass, its acceleration is slow until the force of the spring substantially overcomes the magnetic field force. In the case of drop-out, the effect is dramatic, often resulting in release times an order of magnitude longer than would be expected from abruptly removing the coil voltage.

The undershoot, therefore, may be substantial when measuring drop-out voltage or current. A better way of performing the test is shown in figure 3. In this method a ramp profile using multiple slopes is used. To shorten the overall test time, the coil voltage is stepped down to a "must hold" value and ramped until a change in contact state is detected (not necessarily the transfer point). At this point the ramp is stopped and the contacts again checked after a delay. If the relay contacts have not transferred the ramp is continued at a slower rate until transfer is confirmed



Figure 3

Figure 3 shows the measurement error minimized to an acceptable value. With this ramp profile an excellent trade-off is obtained between test speed and accuracy.